calculated as 0,2025 kW of total irreversibility at the third experiment which was conducted by the smallest condenser. Irreversibility values for medium and big capacity condensers were calculated as 0,1163 kW, and 0,0691 kW respectively. Irreversibility values are small because the cooling capacities of the system were chosen small. According to these results, as the condenser capacity of a system is reduced, the exergy loss of the system increase depending on irreversibility.
Key Words Science Code
: Cooling system, energy analysis, exergy analysis : 626.11.01
calculated as 0,2025 kW of total irreversibility at the third experiment which was conducted by the smallest condenser. Irreversibility values for medium and big capacity condensers were calculated as 0,1163 kW, and 0,0691 kW respectively. Irreversibility values are small because the cooling capacities of the system were chosen small. According to these results, as the condenser capacity of a system is reduced, the exergy loss of the system increase depending on irreversibility.
Key Words Science Code
: Cooling system, energy analysis, exergy analysis : 626.11.01
www.UlusalTezMerkezi.net internet sitesi akademik bilgiye erişimi kolaylaştırmak amacıyla kurulmuştur. YÖK ile herhangi bir bağlantısı yoktur. Tezlerin aranılan anahtar kelime ile ilgili bölümleri adil kullanım hakkı çerçevesinde, kanunlara uygun olarak yayınlanmaktadır. Herhangi bir ticari kar etme amacı olmaksızın sadece bilgiye erişimi hızlandırmak amaçlıdır. Istek, Sikayet, Oneri: [email protected]Tamam